End-winding accelerometers for air- cooled generators based on fibre optic technology that can be used with the Iris Power EVTracII, the GuardII monitoring systems.
Features
- Single or dual axis sensing directions
- Single optical fiber for each sensing axis
- Flexible optical cables
- Dual axis sensor has low cross sensitivity increasing accuracy
- Safe in high voltage and high magnetic fields
- EVAII maximum continuous operation to 200˚C
- Low sensitivity to cable vibration
- Accelerometer reliability extensively evaluated using accelerated life testing at high temperature and high vibration levels
- Electro-Optical Drivers are not mounted on the motor or generator frame, ensuring a longer life and easier maintenance
- Optical Fiber from sensor to Electro- Optical Driver ensuring no RF interference
- Electro-Optical Driver test point enables calibration with fine adjust buttons
- Any EVAII sensor can be paired with any EOD
- Calibrated using Back-to-Back comparison per ISO 16063-21
- Standard 100 mV/g electrical output compatible with any standard vibration monitoring instrument
Options
- 6 single axis sensors
- 7 single axis sensors (6 for the endwinding, one for the stator core)
- 13 single axis sensors (12 for the endwinding, one for the stator core)
- 6 dual axis sensors
- 6 dual axis sensors for the endwinding, plus one single axis sensor for the stator core
- 12 dual axis sensors for endwinding, plus one single axis sensor for the stator core
- EVA installation material included with all sensor kits